BM200 Series Safety Isolation Barrier

BM200 isolated safety barrier can transmit signals between the safe area and the dangerous area, and limit the energy transfer from the safe area to the dangerous area caused by the fault. The voltage, current, temperature, resistance signals generated by the equipment (transmitter) on the dangerous side are isolated and converted into corresponding linear voltage and current signals outputting to the safe area. The product requires independent power supply, and the input/output/power supply is isolated. It can be used in current source, two-wire, three-wire transmitter equipment.

  • Szybka i bezpieczna logistyka
  • Próbka dostępna

Features

● Model: BM200-DI/I

● Input Signal: DC0~20mA / 4~20mA

● Output Signal: DC0~20mA / 4~20mA

● Channel Type: 1 in 1 out, 1 in 2 out, 2 in 2 out

● Power Supply: DC20~35V

● 35mm Din Rail Installation

Features

① It can directly isolate the loop signal in the dangerous area from the signal in the safe area;
② It can allow the instrument to be grounded on site, especially there are many protective function circuits, and it allows live maintenance on site;
③ Compared with other devices, analog signal voltage isolator is still very good in signal processing.

Technical Parameter

TypeBM200-DI/I-B11、BM200-DI/I-C12、BM200-DI/I-C22
Channel type1 in 1 out, 1 in 2 out, 2 in 2 out
Input typeCurrent
Output signal0~20mA/4~20mA (Distribution voltage: 14.0V/20mA)
Output Signal0~20mA /4~20mA (safety side output); Load resistance: ≤550Ω
Transmission accuracy0.2%
Temperature drift50ppm
Response time5ms to reach 90% of final value
Supply voltage20~35V DC
Consumption24V power supply, 20mA output: ≤70mA (one in, one out)≤110mA (one in, two out)≤160mA (two in and two out)
Working temperature-20℃~+60℃
Storage temperature-40℃~+80℃
Relative humidity≤95%RH, no condensation, no corrosive gas place
Altitude≤2500m
Protection levelIP20
WeightAbout 110g (12.5mm shell)About 150g (22.5mm shell)
InstallationDin-rail mounted
Dielectric strengthIntrinsically safe end and non-intrinsically safe end ≥ 2500V AC; power supply and non-intrinsically safe end ≥ 500V AC

Dimension

Wiring

BM200-DI/I-B11

BM200-DI/I-C12

BM200-DI/I-C22

Structure

Photos on Site