APM521 Multifunctional Panel Meter

APM521 network power meter (hereinafter referred to as the meter) is designed according to IEC international standards, featuring full electrical quantity measurement, energy statistics, power quality analysis, event logging functions, and network communication capabilities. It is primarily used for comprehensive monitoring of power supply quality in power grids. This series of meters is equipped with DI/DO modules and AO modules that offer a wealth of functions, allowing for flexible implementation of full electrical quantity measurement and monitoring of switch statuses in electrical circuits.

  • Szybka i bezpieczna logistyka
  • Próbka dostępna

Warning: Undefined array key 0 in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

Warning: Attempt to read property "dup_id" on null in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

Features

● Cut-Out Size: 88*88mm

● Full Power Measurement

● Power Quality Analysis

● Panel Mounted or Din Rail Installation (optional “R”)

● Support Modbus-RTU / Modbus-TCP Communication (optional “E”)

● Accuracy: Class 0.2S (with 1A/5A CT), Class 1 (with 100mV Rogowski Coil)

● Application: Building EMS and complete set cabinet, Malaysia Max Demand Monitoring

Technical Parameters

ItemPerformance Parameters
VoltageRated voltage (UL、CE)66VAC L-N 115VAC L-L 230VAC L-N 400VAC L-L 277VAC L-N 480VAC L-L 400VAC L-N 690VAC L-L
Rated voltage (CPA)3P3L3P4L
3x100V 3x380V 3x690V3x57.7/100V 3x220/380V 3x400/690V
Overload1.2 times rating (continuous); 2 times the rating for 1 second
Power consumption<1VA
Accuracy classError ±0.2%
CurrentRated current (UL、CE)1A、5A
Rated current (CPA)0.015-0.075(6)A (Active energy); 3X1(6)A (Reactive energy)
Overload1.2 times rating (continuous); 10 times the rating for 1 second
Power consumption< 0.2VA
Accuracy classError ± 0.2%
PowerActive, reactive, apparent power, error ± 0.2%
Grid frequencyUL、CE50Hz / 60Hz, error ± 0.2%
CPA50Hz, error ± 0.2%
Response rate≤ 200ms (voltage, current, power)
≤ 1s (electrical energy)
Measurement category66ULN (+20%) 115ULL (+20%) CATⅢ230ULN (+20%) 400ULL (+20%) CATⅢ277ULN (+20%) 480ULL (+20%) CATⅢ400ULN (+20%) 690ULL (+20%) CATⅡ
MeteringElectric energyActive energy: Class D (0.2S); Reactive energy (Class 2 accuracy)
Auxiliary power supplyAC/DC 85-300V
power consumption ≤ 4W、10VA
Electromagnetic compatibilityElectrostatic discharge immunity Class IV
Electrical fast transient burst immunity Class IV
Surge (shock) immunity Class IV
SecurityPower frequency withstand voltageBetween communication and signal input, AC4kV 1min
Insulation resistanceInput and output terminals to casing >500MΩ
CommunicationInterface and communication protocolRS485 interface and Modbus RTU protocol
Communication address rangeModbus RTU: 1~ 247;
Baud rateSupport 1200bps-38400bps
EnvironmentOperating temperature-40℃~+70℃
Storage temperature-40℃~+80℃
Relative humidity≤95% (without condensation)
Altitude≤2000m
≥2000m, ≤5000mOnly applicable to the power supply with the voltage range of AC/DC 85-265V and the voltage below 277/480V.
Installation environmentIndoor use (dry location)
IP ratingIP54 (Front panel), IP30 (Body)
Pollution degreeClass 2
Overvoltage categoriesOVC III
Reference standardULCAN/CSA C22.2 NO.61010-1-12 UL 61010-1 CSA C22.2 No.61010-2-030 UL 61010-2-030
IEC、CEIEC 61010-1 IEC EN 61010-2-30
CPAGB/T17215.321-2021 GB/T17215.323-2022

Dimension

Panel Mounted

Din Rail Installation

Wiring

Wiring sample of current and voltage

Typical Connection