AM2SE Protection Relay

● A complete set of protection, related to the application; ● 4 current input, 3 voltage input, 8DI, 5DO; ● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V, DC48V, DC24V; ● 1 RS485 serial communication, IEC60870-5-103 and Modbus-RTU; ● More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records; ● Powerful graphic programmable Logic.

  • Szybka i bezpieczna logistyka
  • Próbka dostępna

Warning: Undefined array key 0 in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

Warning: Attempt to read property "dup_id" on null in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

General

AM2SE protection relay has the modular design and it can be optimized to feeder protection applications in medium voltage distribution systems. The relay is widely used in substations, hospitals, schools, commercial plazas, large buildings and so on.
Industrial-grade components with professional EMC design. High-performance processor with large capacity RAM and Flash for advanced data processing.

Appearance

AM2SE-H (Horizontal version)
AM2SE-V(Vertical version)

LCD Display

Technical Parameter

ModelAM2SE
Power Supply
Rated voltageAC/DC 110V or AC/DC 220V or DC48V or DC24V
RangeRated voltage × (1±20%)
Burden≤10W ( DC )
PT Inputs
Rated valueAC 100V or 100/√V
PT rated secondary range1V~120V
Accuracy0.5S
Burden≤0.5VA (each phase)
Voltage withstandContinuous: 1.2 Un10s: 2 Un
Phase CT Inputs(Protection Current)
CT rated secondary rangeAC 5A or 1A
Dynamic0.04 ~ 15 × CT rated current
Accuracy0.5S
Burden≤0.5VA (each phase)
Thermal withstandContinuous: 2 In1s: 40 In
Frequency
Rated frequency50Hz or 60Hz
Frequency range45 ~ 65Hz
Accuracy±0.1Hz
Digital Inputs
Operating nominal voltageAC/DC 110V or AC/DC 220Vor DC48V or DC24V
Voltage threshold70% of nominal voltage
Reset threshold55% of nominal voltage
Burden≤ 1W (each phase) (DC220V)
Digital Outputs
Make and carry≥ 10000 operations
Making capacity≥ 1000W, L / R = 40ms
Continuous current≥ 5A
Short duration carry current≥ 30A for 200ms
Breaking capacity≥ 30W, L/R = 40ms

Functions

Front Panel & Dimension

Typical Connection