{"id":4528,"date":"2026-10-19T01:45:40","date_gmt":"2026-10-19T01:45:40","guid":{"rendered":"https:\/\/acrel.pl\/?post_type=product&p=4528"},"modified":"2026-10-19T03:12:40","modified_gmt":"2026-10-19T03:12:40","slug":"aim-m300-medical-insluation-monitor","status":"publish","type":"product","link":"https:\/\/acrel.pl\/ru\/product\/aim-m300-medical-insluation-monitor\/","title":{"rendered":"AIM-M300 Medical Insluation Monitor"},"content":{"rendered":"\n
Acrel AIM-M300 medical intelligent insulation monitor the insulation resistance of medical IT system, At the same time, the load current and temperature of the IT system transformer is monitored. In combination with ASG100, AIL100 series insulation fault locators and the appropriate measuring current transformers, the AIM-M300 is designed to support insulation fault location.AIM-M300 series medical intelligent monitoring device adopts advanced micro-controller technology, which has high integration, compact size, convenient installation and integrates intelligence, digitalization and networking in one. It is suitable for insulation monitoring of isolation power system in Class 2 medical locations such as operating room and intensive care unit.<\/p>\n\n\n\n
| AUX Power<\/td> | Voltage<\/td> | DC 18\u202636V<\/td><\/tr> |
| Power consumption<\/td> | \u22646W<\/td><\/tr> | |
| Insulation Monitoring<\/td> | Resistance measuring range<\/td> | 15\u2026999k\u03a9<\/td><\/tr> |
| Response value<\/td> | 50\u2026999k\u03a9<\/td><\/tr> | |
| Relative uncertainty<\/td> | \u00b110%,\u00b110K<\/td><\/tr> | |
| Response time<\/td> | \u22643s<\/td><\/tr> | |
| Permissible system leakage capacitance Ce<\/td> | \u22645uF<\/td><\/tr> | |
| Measuring voltage Um<\/td> | \u226412V<\/td><\/tr> | |
| Measuring current Im<\/td> | \u226450uA<\/td><\/tr> | |
| Impedance Zi<\/td> | \u2265200k\u03a9<\/td><\/tr> | |
| Internal DC resistance Ri<\/td> | \u2265240k\u03a9<\/td><\/tr> | |
| Permissible extraneous DC voltage Ufg<\/td> | \u2264DC280V<\/td><\/tr> | |
| Temperature monitoring<\/td> | Thermal resistor<\/td> | 2 Pt100<\/td><\/tr> |
| Measuring range<\/td> | -50~+200\u2103<\/td><\/tr> | |
| Alarm value range<\/td> | 0~+200\u2103<\/td><\/tr> | |
| Current Monitoring<\/td> | Alarm Value<\/td> | 5\u202660A<\/td><\/tr> |
| Measuring accuracy<\/td> | \u00b15%<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\nOutline and Dimension<\/strong><\/h2>\n\n\n\n <\/figure>\n\n\n\nWiring<\/strong><\/h2>\n\n\n\n <\/figure>\n\n\n\n24V, G for the auxiliary power supply, and L1, L2 are connected to the IT system (which can be connected to the two output terminals of isolation transformer). I0, I1 for the current transformer signal input, and T0, T1 as the temperature sensor signal input. KE, FE are the functional grounding wires, which should be connected to the on-site equipotential terminals by two independent wires.<\/p>\n\n\n\n Typical Connection<\/strong><\/h2>\n\n\n\n <\/figure>\n","protected":false},"excerpt":{"rendered":"\u2022 Insulation monitoring for medical IT systems, range:10-999kO\n\u2022 Adjustable response value for insulation monitoring\n\u2022 Load and temperature monitoring for IT system transformers\n\u2022 Adjustable load current and temperature response value\n\u2022 Self monitoring with automatic alarm\n\u2022 IT system, PE connection monitoring\n\u2022 Locating current injector for insulation fault location systems(AIM-M300\/SG)\n\u2022 Two relays\n\u2022 1 RS485, Modbus-RTU protocol,1 CAN, internal protocol\n\u2022 Up to 20 fault message memory","protected":false},"featured_media":4530,"template":"","productcat":[8,57],"class_list":["post-4528","product","type-product","status-publish","has-post-thumbnail","hentry","productcat-insulated-power-distribution","productcat-medical-it"],"yoast_head":"\n |