● Insulation fault location in AC IT systems ● AIL150-4: 4 measuring channels ● AIL150-8: 8 measuring channels ● LED indicators: On, Com ● CAN bus ● Auxiliary power supply: DC24V
AIL150-4/AIL150-8 insulation fault locator uses high-precision signal detection circuit with high sensitivity transformer. It detects ASG150 test signal generator' s signal which is injected into the system. It can accurately locate the insulation fault circuit. Among them, AIL150-4 insulation fault locator can locate insulation faults of four loops, AIL150-8 insulation fault locator can locate insulation faults of eight loops.
* Insulation fault location in medical IT systems.
* 4 or 8 channels with measuring current transformer per AIL150.
* Up to 16 measuring channels can be combined by can bus in one medical IT system.
* Aresponse time of up to 2 s in medical IT system acc. to IEC61557-9.
| Parameter | Value | ||
| AIL150-4 | AIL150-8 | ||
| Auxiliary power | Voltage | DC24V(±25%) | |
| The maximum power consumption | ≤2VA | ||
| Monitored system | Rated voltage | 0-242VDC | |
| Frequency | 45-60HZ | ||
| Location signals | Location voltage | <25V | |
| Location current | <1mA | ||
| Fault location | the maximum number of loops | 4 | 8 |
| Response time | <2S | ||
| Communication | Bus | CAN | |
| Protocol | Custom protocol | ||