ARB4 Arc Flash Protection Relay

● Power supply: AC/DC220V, AC/DC110V, DC48V ,DC24 ● Voltage range: 0.1 ~ 120V ● Rated current: AC 5A/1A ● Rated frequency: 50Hz or 60Hz ● Digital Input / Digital Output

  • Быстрая и безопасная логистика
  • Образец доступен

Warning: Undefined array key 0 in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

Warning: Attempt to read property "dup_id" on null in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

General

Acrel ARB4 series arc protection device integrates multiple functions such as protection, measurement, monitoring, control, communication, fault recording, event recording, etc. It can monitor arc signals, protect current or voltage signals in real time, and achieve arc protection function for 0.4kV~35kV medium and low voltage distribution systems.

Technical Parameter

 Model / FunctionARB4-A1ARB4-A2ARB4-A3
HardwareArc sensor signal acquisition123
Current signal aquisition1 set of 3-phase currents,  total of  4 current channels
Voltage signal acquisition3 zero sequence voltages, a total of 3 voltage channels
Digital Input8
Digital Output5 normally open relay outputs
485 interface1
FunctionArc protectionArc criterion√
Arc&Current criterion√
Arc&Zero-sequence Voltage criterion√
Arc monitoring and fault location√
Real time self inspection of arc sensors and fiber optic links√
failure protection√
CT disconnection monitoring√
non-electricity protection√
Device abnormal alarm√
Maintenance status lock√
Fault recording√
ProtocolModbus√
IEC101√
IEC103√
IRIG-B√

Electromagnetic compatibility performance

Test itemRequirement
1Radiation emission limit testGB/T 14598.26IEC 60255-26IEC 61000-6-3IEC 61000-6-4
2Conduction emission limit testGB/T 14598.26IEC 60255-26IEC 61000-6-3IEC 61000-6-4
3Radio-frequency electromagnetic field radiation immunityMeet the requirements of IEC 60255-26,severity is 10V/m.
4Electrostatic discharge immunityMeet the requirements of IEC 60255-26,severity is IV level.
5Disturbance immunity of RF Field Induction conductionMeet the requirements of IEC 60255-26, severe grade disturbance level is 10V.
6Immunity of electric fast transient pulse groupMeet the requirements of IEC 60255-26,severity is IV level.
7Slow-damped oscillation wave immunityMeet the requirements of IEC 60255-26,the common mode is 2.5 and the difference module is 1.
8Surge immunityMeet the requirements of IEC 60255-26,severity is IV level.
9Effect test of AC and DC voltage sag interruptionGB/T 14598.26IEC 60255-26
10Power frequency magnetic field immunityMeet the requirements of IEC 60255-26,severity is V level.

Typical Connection

ARB series arc protection relay application
ARB6 Arc Flash Protection Relay - network

Installation

ARB6 Arc Flash Protection Relay - installation in busbar room
ARB6 Arc Flash Protection Relay - installation in handcart room
ARB6 Arc Flash Protection Relay - installation in cable room

Installation

ARB4 Arc Flash Protection Relay Installation - 1
ARB4 Arc Flash Protection Relay Installation - 2

Outline and Dimension

ARB4 Arc Flash Protection Relay Dimension
ARB6 Arc Flash Protection Relay - installation of arc probe

On-site Pictures

ARB6 Arc Flash Protection Relay - on-site picture - 1
ARB6 Arc Flash Protection Relay - on-site picture - 2