AMC96L-AV3 Three Phase AC Voltage Meter

AMC series meters adopt AC sampling technology, which can measure the current ,voltage,power, power factor and electric energy parameters in the power grid separately. It can set the magnification through the panel membrane switch. The meters have RS485 communication interface, adopt Modbus protocol; also can convert the power signal into a standard DC analog signal.

  • Быстрая и безопасная логистика
  • Образец доступен

AMC96L-AV3

    • Communication:RS485 (Modbus-RTU)
    • Display:LCD display, set multiplying power
    • Rated U:AC voltage: AC 100V, 220V, 380V
    • 1600-160000imp/kWh
        • 45-65Hz


Datasheet


Technical Parameters
Value
InputConnection

Single phase-2 wire,3 phase-3 wire,3 phase 4-wire

Frequency45-65Hz
Voltage

Rating:

Single-phase:AC 100V、400V

Three-phase:AC 3x57.7V/100V(100V)、3x220V/380V(400V)

3x380V/660V(660V)(96 size only)

Note:72 profile not suitable for high voltage application


Overload:1.2 fold rating(continuous):2 fold rating for 1 second
Power consumption:<0.5VA
Current
Rating:AC 1A、5A
Overload:1.2 fold rating(continuous):10 fold rating for 1 second
Power consumption:<0.5VA
OutputElectric energyOutput mode:open-collector photo-coupler pulse
Pulse constant:10000imp/kWh(settable),see wiring diagram for details
CommunicationRS485 port,Modbus-RTU protocol,DLT645 protocol(versions 09 and 97),baud rate 1200-38400
FunctionSwitching inputDry contact input,built-in power supply
Switching outputOutput mode:Relay normally open contact output
Contact capacity:AC 250V/3A、DC 30V/3A
Analog output
1-5V,4-20mA
Accuracy Class

Frequency:0.05Hz,Current、Voltage;0.2 class,Reactive

Power:1.0 class,Reactice Electric energy:1.0 class active

Power:0.5 class,active electric energy:0.5 class,2-31th harmonic

measurement:±1%

Power SupplyAC/DC 85-265V     Power consumption≤10VA
Security

Power frequency

withstand voltage

Between Power supply//Switching Output//Current input//voltage input and

Transmitting//Communication//Pulse Output//switching input AC 2kV 1min;

Between Power supply、switching output、Current input、voltage input AC 2kV 1min;

Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min;

Insulation resistanceInput、Output end to machine enclosure>100MΩ
EnvironmentTemperaturework:-25℃~+65℃ storage:-40℃~+80℃
Humidity≤93%RH Non-condensing
Altitude≤2500m


Dimension


default-image


Wiring


default-image


Network

default-image


Installation


default-image