Wireless Temperature Monitoring System Решение

The wireless temperature monitoring system is mainly used for real-time online monitoring of the temperature of electrical connection points such as cable joints, circuit breaker contacts, busbars, etc. in high and low voltage switch cabinets to prevent excessive contact resistance and heating caused by oxidation, looseness dust and other factors during operation, thereby improving equipment safety, accurately reflecting equipment operating status, and reducing equipment accident rates.

Wireless Temperature Monitoring System


Overview


The wireless temperature monitoring system is mainly used for real-time online monitoring of the temperature of electrical connection points such as cable joints, circuit breaker contacts, busbars, etc. in high and low voltage switch cabinets to prevent excessive contact resistance and heating caused by oxidation, looseness,dust and other factors during operation, thereby improving equipment safety, accurately reflecting equipment operating status, and reducing equipment accident rates.


Architecture


default-image

Application Scenarios


• Municipal Engineering
• Data Centre 
• Chemical Industry 
• Metallurgical Industry
• Petroleum 
• Traffic Industry 
• Industrial and Mining Enterprise


Typical Solutions


⚫ High voltage Switchgear Temperature Monitoring
default-image

Product

Application

Installation size


picturejsu 

1.Cable connector temperature measurement

2.Contact temperature measurement

3.Busbar temperature measurement

25.82*20.42*12.8mm
(length*width*height)


⚫ Low Voltage Power Cabinet

default-image

Product

Application

Installation size


图片3ow0 

ATE400

1.CB connector/busbar temperature measurement

2.Drawer cabinet cable joints temperature measurement

25.82*20.42*12.8mm
(length*width*height)

图片4vjj 
ATE300M

Surface temperature measurement of capacitors/reactances

35mm din-rail

图片57lc 
ACE100-29

Temperature measurement of low-voltage outgoing cable joints

67.7*57.4*69.8mm
(length*width*height)


⚫ Transformer

default-image

Product

Application

Installation size


图片3435 

Transformer connector temperature measurement

25.82*20.42*12.8mm
(length*width*height)

图片7e10 

Transformer internal winding temperature measurement

Embedded installation


⚫ Other Devices

default-image

Product

Application

Installation size

图片102i0 
ATE300P

Temperature measurement of motor surface

70*65*45.5mm,L=2m
(length*width*height, probe wire length)


图片37vw 

ATE400

Temperature measurement of motor junction box

25.82*20.42*12.8mm
(length*width*height)

图片7xy0 
ARTM-8L (Pre-embedded PT100)

Temperature measurement of internal winding of motor

Embedded installation


Photo On Site

default-image


Related Products


Product

Features

Application

图片161o 

ATE300P

• Wireless frequency:433/470MHz

• Communication distance:500m in open area

• Sampling frequency:25s

• Transmitting frequency:25s-5min

• Power source:Battery

• Installation:Rail type/Tie type

• Range of temperature:-50℃~+300℃

• Precision :±1℃

• Battery life:≥5 years(25℃)

• Protection level:IP65


Motor surface,busduct shell .etc.


图片22g8 

ATE400

• Wireless frequency:433/470MHz 

• Wireless transmission distance, 150 meters; 

• Fase sampling frequency, 15s;

• CT-powered, more than 5A starting current;

• Widely temperature measuring range, -50℃~125℃.

Circuit breaker moving contacts, static contacts, busbars, cables, etc.

图片3v8q 


ATE300M

• Wireless frequency:433-510MHz

• Communication distance:1000m in open area

• Sampling frequency:1-240s

• Power source:AC/DC 85~265V

• Installation:Rail type/Tie type

• Range of temperature:-40℃~+140℃

• Precision:±1℃

• Probe:optioanl 1-6 circuits

Low-voltage copper bars, cables, capacitors, reactance, etc.

图片43qh 

ACE100-29

• Temperature Range:-50℃~125℃

• Current Range:1~400A,AC

• Temperature Precision:±1℃

• Current Precision:1%FS

• Sampling & Transmission cycle:CT-powered:10~30S;Battery:3min

•CT-powered, starting current:≥2.5A,AC

• Battery life:3 years(25℃),Replaceable(CR2450)

• Wireless frequency:470Mhz/433Mhz

• Communication distance:150m in open area

• Environment:-40~+85℃;≤95% RH

Low voltage cable with diameter 6~29mm

图片5i0u 

AHE100

• Range of temperature:-30℃~+85℃

• Range of humidity:±30%RH

• Temperature Precision:±1℃

• Sampling frequency:25s

• Transmitting frequency:5min

• Communication distance:500m in open area

• Battery life:3years(In 25℃ environment)Replaceable(model CR2450)


The environment inside medium and high voltage switch cabinets, terminal boxes, ring main units, box-type transformers and other equipment and in power distribution rooms

图片6zm7 

ATC600

• Power supply:AC/DC 85~265V or DC 12-48V

• One channel RS485,modbus-rtu protocol

ATC600-C:Maximum recieve 240 pcs ATE400/ACE100-29/AHE100 data
ATC600-Z:Work with ATC600-C to transmit data
ATC600-M:Maximum recieve 240 pcs ATE300M data

图片7x83

ARTM-PN

• Wireless temperature measurement, 60 points;

• U, I, P, Q, f, Ep, Eq measurement;

• 4 digital inputs;

• 2 alarm relays, high-temperature alarm;

• LCD display;

• Power supply:AC85-265 Or DC100-300V

• 1 RS485 communication, Modbus-RTU.


Can be installed separately in high-voltage cabinets and low-voltage drawer cabinets. Each device can maximum receive data from 60 sensors

图片8nsf 

ARTM-8

• Working power supply: AC 85-265V or DC 100-300V

• Installation: embedded installation

• Communication:1-Channel RS485 interface ,Modbus-RTU protocol

• Temperature measurement range: -200℃~600℃

• Contact temperature measurement accuracy: 0.5 level

• Alarm output: 2 channels

• Output capacity: AC 250V/ 5A, DC 30V/ 5A

Can be connected to 8 channels of PT100 temperature signals. Suitable for contacts in high and low voltage switch cabinets, transformer windings, motor windings and other thermal power plants, hydropower stations and other occasions.

图片98yn 

ARTM-8L

• Working power supply: AC85~265V/DC100-300V

• Installation method: embedded installation

• Communication interface: 1-channel RS485 interface (Modbus-RTU protocol)

• 8 channelsPT100/PT1000/NTC

• Alarm output: 5 channels

• Output capacity: AC 250V/ 5A, DC 30V/ 5A

• Temperature and humidity input: optional 1 channel, temperature accuracy ±1℃, humidity accuracy ±3%

• Transmission output: 3 channels, 4~20mA

Contacts in high and low voltage switch cabinets, transformer windings, motor windings,suitable for temperature measurement in other thermal power plants, hydropower stations and other occasions.

图片10hct

ARTM-24

• Working power supply: AC85~265V/DC100-350V

• 24 Channels Sensor connect

• Installation method: guide rail installation

• Communication interface: 1-Channel RS485 interface (Modbus-RTU protocol)

• Temperature accuracy: ±1℃; humidity accuracy: ±3%

• Alarm output: 2 channels are normally open, corresponding to the low alarm value and high alarm value of each channel respectively.

• Output capacity: AC 250V/ 5A, DC 30V/ 5A

Contacts in high and low voltage switch cabinets, transformer windings, motor windings and other thermal power plants. suitable for temperature measurement in hospitals, hydropower stations and other places.

图片11qnw

HMI Touch Screen

• Touch screen model:ATP007,ATP010

• Touch screen/transceiver operating power supply:DC 24V(±10%),15W

• Temperature measurement range:-50℃~125℃

• Temperature accuracy:±1℃

• Sensor battery span:≥5 years

• Communication Port:RS485/Ethernet MODBUS-RTU

• Communication Protocol:MODBUS-RTU/ MODBUS-TCP

• Operating temperature:-10℃~55℃


Can be embedded in high-voltage cabinets and low-voltage drawer cabinets. which can upload the collected temperature data to the monitoring center.