AMC96L-E4/KC Multifunction AC Power Meter

AMC series meters adopt AC sampling technology, which can measure the current ,voltage,power, power factor and electric energy parameters in the power grid separately. It can set the magnification through the panel membrane switch. The meters have RS485 communication interface, adopt Modbus protocol; also can convert the power signal into a standard DC analog signal.

  • Fast And Safe Logistics
  • Sample Available

AMC96L-E4/KC

    • True RMS Measurements
    • THD with 2-31st Harmonics
    • Max/Min Log with Timestamp
    • Internal Optional 4DI&2DO or 2DI&2DO&2AO
        • Standard one Energy Pulse Output


Features


Accuracy

Active energy: Class 0.5


Frequency

45-65Hz


Power Supply:

AC/DC 85~265V


Consumption

Voltage: Power consumption <0.5VA;
Current: Power consumption< 0.5VA;
Auxiliary power supply:power consumption≤10VA


Technical ParametersValue
InputConnectionSingle phase-2 wire,3 phase-3 wire,3 phase 4-wire
Frequency45-65Hz
VoltageRating: Single-phase:AC 100V、400V Three-phase:AC 3x57.7V/100V(100V)、3x220V/380V(400V) 3x380V/660V(660V)(96 size only) Note:72 profile not suitable for high voltage application

Overload:1.2 fold rating(continuous):2 fold rating for 1 second
Power consumption:<0.5VA
CurrentRating:AC 1A、5A
Overload:1.2 fold rating(continuous):10 fold rating for 1 second
Power consumption:<0.5VA
OutputElectric energyOutput mode:open-collector photo-coupler pulse
Pulse constant:10000imp/kWh(settable),see wiring diagram for details
CommunicationRS485 port,Modbus-RTU protocol,DLT645 protocol(versions 09 and 97),baud rate 1200-38400
FunctionSwitching inputDry contact input,built-in power supply
Switching outputOutput mode:Relay normally open contact output
Contact capacity:AC 250V/3A、DC 30V/3A
Analog output1-5V,4-20mA
Accuracy ClassFrequency:0.05Hz,Current、Voltage;0.2 class,Reactive Power:1.0 class,Reactice Electric energy:1.0 class active Power:0.5 class,active electric energy:0.5 class,2-31th harmonic measurement:±1%
Power SupplyAC/DC 85-265V     Power consumption≤10VA
SecurityPower frequency withstand voltage

Between Power supply//Switching Output//Current input//voltage input and

Transmitting//Communication//Pulse Output//switching input AC 2kV 1min;

Between Power supply、switching output、Current input、voltage input AC 2kV 1min; Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min;
Insulation resistanceInput、Output end to machine enclosure>100MΩ
EnvironmentTemperaturework:-25℃~+65℃ storage:-40℃~+80℃
Humidity≤93%RH Non-condensing
Altitude≤2500m


Dimension


default-image


Wiring


default-image


Network

default-image


Installation


default-image