ASJ10L-LD1A Leakage Current Protection Relay

● The measurement of AC type after-current; ● The streamer display of current percentage; ● The setting of rated residual action current; ● The setting of non-driving time of limitation; ● Two-pair relay output; ● Possessing the function of on-the-spot and long-distance testing and resetting.

  • Szybka i bezpieczna logistyka
  • Próbka dostępna

Warning: Undefined array key 0 in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

Warning: Attempt to read property "dup_id" on null in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

General

ASJ Series of action relay of after-current, low-voltage circuit break or low-voltage contactor can be made up for combined after-current production device, which is mainly applied for the TT and TN system distributing circuit with the alternating current 50Hz, the rated voltage 400V or below.
ASJ Series of action relay of after-current is applied in the earth fault protection for the electric circuit, so as to prevent the equipment damage and the fire accident of electric equipment caused by the ground fault current, moreover, it also can provide indirect contact protection against the electric shock risk.

Function

Relay TypePanel size (mm)Shell size (mm)Hole size(mm)
ASJ20-LD1CASJ20-LD1A48×48( width by height)43.8×43.8×100(width by height by depth)45×45(width by height)
ASJ10-LD1CASJ10-LD1AASJ10L-LD1A85×54×64(length by width by height)

Technical Parameter

InputRated residualoperated current I△n0.03, 0.05, 0.1, 0.3, 0.5, 1, 3, 5, 10, 30(A)
Limitation non driving time0,0.06, 0.1, 0.2, 0.3, 0.5, 0.8, 1, 4, 10(S)
Rated non-action residual current50%I△n
Frequency50Hz±5Hz
Tripping accuracy-20% ~ -10%I△n
OutputOutput mode1 normal changeover contact
Contact capacityAL1: 8A 250VAC 5A 30VDCAL2: 6A 250VAC 5A 30VDC
Reset modeLocal, remote, automatic
Auxiliary power supplyVoltage rangeAC/DC85~270V
Power consumption≤5W
Power frequency withstand voltageThe effective value of alternating current between the power supply, input and output: 2kV/1min

Dimension

Appearance and hole size of installation (ASJ10L-LD1A)
Installation mode of magnetic ring

Wiring

Typical Connection

Collect switch signals by PLC and upload to monitoring system