APView350 Power Qualtiy Monitor Analyzer

● High-performance hardware platform ● Various interfaces available ● 4-way AC voltage, 4-way AC current ● 3-channel DO, 5-channel DI ● 2 RS485 interfaces supporting the Modbus RTU protocol and the IRIG-B protocol ● 2 Ethernet interfaces supporting Modbus TCP, IEC 61850 MMS, FTP and device upgrade ● 1 USB port for device upgrades

  • Szybka i bezpieczna logistyka
  • Próbka dostępna

Warning: Undefined array key 0 in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

Warning: Attempt to read property "dup_id" on null in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

General

The APView350 utilizes a high-performance multi-core platform and an embeddedoperating system. It adheres to the measurement methods for power quality indicesspecified in IEC 61000-4-30, integrating functions such as harmonic analysis, waveformsampling, voltage sag/swell/interruption detection, flicker monitoring, voltage unbalancemonitoring,demand,TOU, event recording, and measurement control. The device meets Class A national standards in terms of measurement methodstandardization, parameter accuracy, clock synchronization, and event alarmfunctionality.

It is suitable for power quality monitoring in 10kV and below power supply systems andisused in renewable energy systems like photovoltaic, energy storage, and wind power.

Naming Rule

Front Panel

Technical Parameter

Power supplyRated voltage: AC/DC 220 V, AC/DC 110 V or DC 24 V/48 V
Permissible deviation: -20 % to +20 %
Power consumption: ≤ 15 W
alternating currentRated current: 5 A
Input method: Current transformer input
Measuring range: 0–1.2 in
Power consumption: ≤ 0.5 VA (single-phase)
Overload capacity: 1.2 In, continuous operation
20 times for 1 second
alternating voltageInput mode: voltage converter input or direct connection
Rated voltage: 57.74V/100V, 220V/380V, 400V/690V
Measuring range: 0–1.2 Un
Power consumption: ≤ 0.5 VA (single-phase)
Overload capacity: 1.2 Un, continuous operation
4 times for 1 second
Digital inputRated voltage: AC/DC 220 V, AC/DC 110 V or DC 24 V/48 V
Input mode: Passive contacts, external power required
Digital outputMechanical lifespan: ≥10000
Output mode: Passive contacts
Switching capacity: ≤4,000 W or ≤384 VA
Forward current: ≥16 A (AC 250 V/DC 24 V) in continuous operation
≥30 A for a short time (200 ms)
communication portEthernetSpeed: 10/100 Mbps, adaptive
Type: 10/100Base-T
Compatible with TCP/IP and FTP protocol
RS485 connectionSpeed: 300–57,600 bps
With optical isolation
Monitor accuracyEffective voltage±0.1 %
RMS current±0.1 %
P,Q,S±0.2%
Power factor±0.5 %
Ep+,Ep-,Eq+,Eq-Class 0.5
Working conditionsNormalOperating temperature: -10 °C to +55 °C
Storage temperature: -30 °C to +80 °C
Relative humidity: 5 % to 95 %
Air pressure: 86–106 kPa
Altitude: ≤ 2500 m
Protection class: IP51

Dimension and Installation

Terminal