● Clamshell design ● Beautiful shape easy wiring ● High accuracy ● Suitable for busbar or cable
Acrel AKH-0.66/I Series Current Transformer can be used together with measuring instruments by collecting AC current signals. The measuring range of primary current is 15-3000A, and the secondary output is 5A or 1A. The measuring range is 5-120% of the rated value. Clamshell design, beautiful appearance, convenient wiring. The cover material is transparent polycarbonate, which can clearly see the secondary lead wiring. Square and square combination of holes, both through the cable, or through the busbar.
Acrel AKH-0.66/I Series Current Transformer can be used together with measuring instruments by collecting AC current signals.
![]() | * Model: AKH-0.66 I Series* Rated secondary current: 1A or 5A* Rated primary current: 10~3000A* Rated voltage: 660V AC* Test voltage: 3kV AC(1min)* Rated frequency: 50/60Hz |
| * Security factor: FS<5* Continuous overload: 120%In* Protection level: IP30* Operating temperature: -25℃~+50℃* Storage temperature: -40℃~+80℃* Relative humidity: ≤90%RH, no condensation | ![]() |
| Specification | Rated Current Ratio(A) | Precision Degree and Corresponding Rated Load (VA) | Straight-Through Tums | Bus Spec(mm)/Number | Max. Cable Outer Diameter (mm) | Installation | ||
| 0.2 | 0.5 | 1 | ||||||
| 30I | 15/5(1) | 1.5 | 5 | / | Ф22 | A | ||
| 20/5(1) | 1.5 | 4 | ||||||
| 25-30/5(1) | 1.5 | 3 | ||||||
| 40-60/5(1) | 1.5 | 2 | ||||||
| 75-100/5(1) | 1.5 | 1 | 30×10/1 | A、B | ||||
| 150-200/5(1) | 2.5 | 1 | ||||||
| 250/5(1) | 3.75 | 1 | ||||||
| 300-450/5(1) | 5 | 1 | ||||||
| 500/5(1) | 10 | 1 | ||||||
| 600/5 | 10 | 1 | ||||||
| 40I | 10/5(1) | 1.5 | 10 | / | Ф30 | A | ||
| 15/5(1) | 1.5 | 8 | ||||||
| 20/5(1) | 1.5 | 5 | ||||||
| 25-30/5(1) | 1.5 | 4 | ||||||
| 40/5(1) | 1.5 | 3 | ||||||
| 50-75/5(1) | 1.5 | 2 | ||||||
| 100/5(1) | 1.5 | 1 | 40×10/1 | A、C | ||||
| 150/5(1) | 2.5 | 1 | ||||||
| 200/5(1) | 2.5 | 1 | ||||||
| 250/5(1) | 3.75 | 1 | ||||||
| 300-450/5(1) | 5 | 1 | ||||||
| 500-800/5(1) | 10 | 1 | ||||||
| 1000/5(1) | 10 | 1 | ||||||
| 60I | 150/5(1) | 2.5 | 1 | 60×10/160×6/1-2 | Ф44 | A、C | ||
| 200-250/5(1) | 2.5 | 1 | ||||||
| 300-450/5(1) | 5 | 1 | ||||||
| 500-800/5(1) | 10 | 1 | ||||||
| 1000-1250/5(1) | 10 | 1 | ||||||
| 1500-2000/5(1) | 20 | 1 | ||||||
| 2500/5(1) | 30 | 1 | ||||||
| 80I | 150/5(1) | 2.5 | 1 | 80×10/1 | Ф50 | A、C | ||
| 200-250/5(1) | 2.5 | 1 | ||||||
| 300-400/5(1) | 5 | 1 | ||||||
| 500-800/5(1) | 10 | 1 | ||||||
| 1000-1250/5(1) | 10 | 1 | ||||||
| 1500-2000/5(1) | 20 | 1 | ||||||
| 2500-3000/5(1) | 30 | 1 | ||||||
| Spec. and size | ![]() | ||||||||
| Type | Outline size | Through size | Mounting size | Tolerance (mm) | |||||
| W | H | D | a | e | Φ | M | N | ||
| 30I | 60 | 78 | 36 | 31 | 11 | 22 | 34 | 57.5 | ±1 |
| 40I | 75 | 95 | 45 | 40 | 11 | 31 | 40 | 57.5 | |
| 60I | 102 | 130 | 45 | 61.5 | 21 | 45 | 42 | 57.5 | |
| 80I | 118 | 140 | 45 | 82 | 11 | 52 | 60 | 57.5 | |
AKH-0.66/I Series Current Transformer can be installed in three ways: A-type straight plate is fixed, B-type bent plate is fixed, and C-type single plate pressure plate is fixed. Note that when the current transformer is in use, the secondary open circuit shall not be allowed, and the secondary outlet S2 shall be grounded.