AID150 Alarm and Display Device

● Remote monitoring ● LED indicators:On, Insulation, Overload, Overtemp ● Mute button ● Test button ● Auxiliary power supply: DC24V ● RS485(MODBUS-RTU)

  • Szybka i bezpieczna logistyka
  • Próbka dostępna

Warning: Undefined array key 0 in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

Warning: Attempt to read property "dup_id" on null in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

General

AID Series alarm and display device is remote display and sound and light alarm device by using advanced fieldbus communications technology. AID Series alarm and display device have four models: AID10, AID120, AID150 and AID200. Products are classified according to the installation method and display. The device can be installed on the operating room or information control panel of intensive care unit, the medical staff can easily know the status of medical isolated power systems, and the type of fault when the system fails.

AID150 centralized alarm and display instrument adopts the LCD liquid crystal display and achieves data exchange with AIM-M200 medical intelligent insulation monitoring instrument through CAN communication interface of self-defined protocol, which can real-time monitor multi-channel data of AIM-M200 medical intelligent insulation monitoring instrument.

Function

* Can read and display monitoring data and alarm information of insulation monitor in real-time by bus communication

* Can set the alarm parameters of insulation monitor remotely

* When the system fails, products can generate sound and light alarm, if you press the mute button, the sound can be turned off, but the corresponding fault indicator does not go out until the fault is removed so far.

Specification

Auxiliary PowerVoltageDC24V
Consumption<0.6W
Load Current Alarm Value Settings14A,18A, 22A, 28A, 35A, 45A
Temperature Alarm Value Range0-200℃
AlarmSound and light alarm
Alarm TypeInsulation fault, overload, over-temperature, equipment failure
CommunicationRS485 interface, Modbus-RTU protocol
DisplayLCD Display


Dimension

Display

Application


Wiring and Installation

Terminal Description

Note: The 24V power supply can be connected by multiple copper wires of 2x1.5mm2, and the RS485 communication terminal can be connected by shielded twisted pair of 2x1.5mm2
Installation

Installation