AM5SE Protection Relay

● A complete set of protection, related to the application; ● 8 current input, 4 voltage input, 16 DI, 10 DO; ● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V; ● 2 RS485 serial communication, IEC 60870-5-101, IEC60870-5-103 and Modbus-RTU; ● 1 RS232 for user update; ● 1 GPS for GPS timing; ● More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records; ● Powerful graphic programmable Logic.

  • Szybka i bezpieczna logistyka
  • Próbka dostępna

Warning: Undefined array key 0 in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

Warning: Attempt to read property "dup_id" on null in /www/wwwroot/acrel.pl/wp-content/plugins/sytech-fronteditor/sytech-fronteditor.php on line 342

General

AM5SE series microcomputer protection device are applicable to the user substation which the input voltage is 35kv or above. AM5 can be used to protect and control the user substation, and is be widely used to Power Industry, Water conservancy industry, Traffic Industry, Oil industry, Chemical industry,Coal Industry, Metallurgical Industry and so on.

Front Panel

LCD Display

Technical Parameter

Rated Characteristics

Characteristics / VersionAM5SE-F,AM5SE-T,AM5SE-M,AM5SE-C,AM5SE-B,AM5SE-D2,AM5SE-D3,AM5SE-TB,AM5SE-MDAM5SE-UB, AM5SE-IS, AM5SE-FE,AM5SE-FA,AM5SE-K
Power Supply
Rated voltageAC/DC 110V or AC/DC 220V
RangeRated voltage × (1±20%)
Burden≤15 VA
PT Inputs
Rated valueAC 100V or 100 √3 VAC 380V or 220V
PT rated secondary range0.1V~120V0.1V ~ 456V
Accuracy0.5S
Burden≤0.5VA (each phase)
Voltage withstandContinuous: 1.2 Un10s: 2 Un
Phase CT Inputs (Protection Current)
CT rated secondary rangeAC 5A or 1A
Dynamic20 × CT rated current
Accuracy0.5S
Burden≤0.5VA (each phase)
Thermal withstandContinuous: 2 In1s: 40 In
Phase CT Inputs (Measurement Current)
CT rated secondary rangeAC 5A or 1A
Dynamic1.5 × CT rated current
Accuracy0.5S
Burden≤0.5VA (each phase)
Thermal withstandContinuous: 1.5 In1s: 4 In
Frequency
Operating nominal voltageAC/DC 110V or AC/DC 220V
Voltage threshold70% of nominal voltage
Reset threshold55% of nominal voltage
Burden≤ 1W (each phase) (DC220V)
Digital Outputs
Make and carry≥ 10000 operations
Making capacity≥ 1000W, L / R = 40ms
Continuous current≥ 5A
Short duration carry current≥ 30A for 200ms
Breaking capacity≥ 30W, L/R = 40ms

Protection characteristics

CharacteristicsAccuracyResolutionDisengaging ratio
Voltage±3%0.001V0.95 and 1.05
Current±3%0.001A0.95 and 1.05
Frequency±0.02Hz0.001Hz
Operation delay|t>(DT)40ms or ±2% setting value0.001s-
Operation delay|t>(IDMT)40ms or ±5% setting value0.001s-

Environmental characteristics

During operation10℃~+55℃, temperature; 5%~95%, humidity
Storage-25℃~+70℃
Altitude≤ 2000m
EnclosureIP20 (local panel)

Product safety

InsulationInsulation resistance >100MΩat 500Vdc
High voltages withstand2kV rms AC, 1 min:between all case terminals connected together, and the case earth/ground;2 kV rms AC, 1 min:between all terminals of independent circuits
Impulse voltage±5kV (1.2/50μs, 0.5J)

Electromagnetic Compatibility Characteristics

CharacteristicsStandardLevel/Class
Radiated emissionIEC-60255-26:2023——5.1A
Conducted emissionIEC-60255-26:2023——5.2A
Radiated radio frequency fieldsIEC-60255-26:2023A
Electrostatic dischargeIEC-60255-26:2023——6.1B
Conducted radio frequency disturbanceIEC-60255-26:2023——6.2-6.5A
Fast transient burstsIEC-60255-26:2023——6.2-6.5B
Slow damped oscillatory wavesIEC-60255-26:2023——6.2-6.4B
SurgesIEC-60255-26:2023——6.2-6.4B
Voltage dips and short interruptions test(AC or DC)IEC-60255-26:2023——6.2A/C 1
Magnetic field at power frequencyIEC-60255-26:2023——6.1B

Function

Installation

Dimension
Cut-out Dimension & Wirng

Typical Connection