● Auxiliary Power Supply: DC24V (±25%) ●Maximum Power Consumption: ≤2VA ●Monitored System Rated Voltage: 0-242VAC ●Monitored System Rated Frequency: 45-60Hz ●Fault Locating Maximum Circuit: 6 Channels ●Fault Locating Response Time: <2s ●Communication Mode: CAN ●Communication Protocol: Customize
AIL160-6 insulation fault locators use high sensitivity transformers with high precision signal detection circuitry to detect the signals injected into the system by the AIM-M300/SG Medical Intelligent Insulation Monitors,and to accurately locate the circuits where the insulation faults are located. The AIL160-6 Insulation Fault Locator can locate insulation faults in 6 circuits. Insulation fault location can be used in combination with up to 48 circuits for the AIL160 series.
• It can cooperate with AIM-M300/SG Medical Intelligent Insulation Monitor to realize the fault location function. The localization results are indicated by the LEDs of the corresponding circuits.
• It adopts CAN bus technology, it can interact data with other devices;
| Auxiliary Power Supply | Rated Voltage | DC 18~36V |
| Maximum Power Consumption | ≤2VA | |
| Monitoring System | Rated Voltage | AC 0~242V |
| Rated Frequency | 45~60Hz | |
| Fault Location | Number of Loops | 4 loops, 8 loops, 6 loops |
| Response Time | ≤5s | |
| Communication Parameters | Communication Method | CAN Communication |
| Communication Protocol | Custom-defined Protocol |



Selection table of insulation fault locator:
| Type | AIL150-4 | AIL150-8 | AIL160-6 |
| Functions | Insulation fault location | ||
| Supply voltage | DC 9V-36V | DC 9V-36V | DC 9V-36V |
| Communication | 1 CAN | 1 CAN | 1 CAN |
| Locating channels | 4ch | 8ch (Maximum 24ch) | 6ch (Maximum 48ch) |
| Dimension | 198X123.6X65(mm) | 215X70X56(mm) | |
| Certifications | CE、IEC | CE、IEC | CE、IEC |
| Standard | IEC61557-9 | ||