● A complete set of protection, related to the application; ● 8 current input, 4 voltage input, 16 DI, 10 DO; ● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V; ● 2 RS485 serial communication, IEC 60870-5-101, IEC60870-5-103 and Modbus-RTU; ● 1 RS232 for user update; ● 1 GPS for GPS timing; ● More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records; ● Powerful graphic programmable Logic.
AM5SE series microcomputer protection device are applicable to the user substation which the input voltage is 35kv or above. AM5 can be used to protect and control the user substation, and is be widely used to Power Industry, Water conservancy industry, Traffic Industry, Oil industry, Chemical industry,Coal Industry, Metallurgical Industry and so on.


Rated Characteristics
| Characteristics / Version | AM5SE-F,AM5SE-T,AM5SE-M,AM5SE-C,AM5SE-B,AM5SE-D2,AM5SE-D3,AM5SE-TB,AM5SE-MD | AM5SE-UB, AM5SE-IS, AM5SE-FE,AM5SE-FA,AM5SE-K |
| Power Supply | ||
| Rated voltage | AC/DC 110V or AC/DC 220V | |
| Range | Rated voltage × (1±20%) | |
| Burden | ≤15 VA | |
| PT Inputs | ||
| Rated value | AC 100V or 100 √3 V | AC 380V or 220V |
| PT rated secondary range | 0.1V~120V | 0.1V ~ 456V |
| Accuracy | 0.5S | |
| Burden | ≤0.5VA (each phase) | |
| Voltage withstand | Continuous: 1.2 Un10s: 2 Un | |
| Phase CT Inputs (Protection Current) | ||
| CT rated secondary range | AC 5A or 1A | |
| Dynamic | 20 × CT rated current | |
| Accuracy | 0.5S | |
| Burden | ≤0.5VA (each phase) | |
| Thermal withstand | Continuous: 2 In1s: 40 In | |
| Phase CT Inputs (Measurement Current) | ||
| CT rated secondary range | AC 5A or 1A | |
| Dynamic | 1.5 × CT rated current | |
| Accuracy | 0.5S | |
| Burden | ≤0.5VA (each phase) | |
| Thermal withstand | Continuous: 1.5 In1s: 4 In | |
| Frequency | ||
| Operating nominal voltage | AC/DC 110V or AC/DC 220V | |
| Voltage threshold | 70% of nominal voltage | |
| Reset threshold | 55% of nominal voltage | |
| Burden | ≤ 1W (each phase) (DC220V) | |
| Digital Outputs | ||
| Make and carry | ≥ 10000 operations | |
| Making capacity | ≥ 1000W, L / R = 40ms | |
| Continuous current | ≥ 5A | |
| Short duration carry current | ≥ 30A for 200ms | |
| Breaking capacity | ≥ 30W, L/R = 40ms | |
Protection characteristics
| Characteristics | Accuracy | Resolution | Disengaging ratio |
| Voltage | ±3% | 0.001V | 0.95 and 1.05 |
| Current | ±3% | 0.001A | 0.95 and 1.05 |
| Frequency | ±0.02Hz | 0.001Hz | |
| Operation delay|t>(DT) | 40ms or ±2% setting value | 0.001s | - |
| Operation delay|t>(IDMT) | 40ms or ±5% setting value | 0.001s | - |
Environmental characteristics
| During operation | 10℃~+55℃, temperature; 5%~95%, humidity |
| Storage | -25℃~+70℃ |
| Altitude | ≤ 2000m |
| Enclosure | IP20 (local panel) |
Product safety
| Insulation | Insulation resistance >100MΩat 500Vdc |
| High voltages withstand | 2kV rms AC, 1 min:between all case terminals connected together, and the case earth/ground;2 kV rms AC, 1 min:between all terminals of independent circuits |
| Impulse voltage | ±5kV (1.2/50μs, 0.5J) |
Electromagnetic Compatibility Characteristics
| Characteristics | Standard | Level/Class |
| Radiated emission | IEC-60255-26:2023——5.1 | A |
| Conducted emission | IEC-60255-26:2023——5.2 | A |
| Radiated radio frequency fields | IEC-60255-26:2023 | A |
| Electrostatic discharge | IEC-60255-26:2023——6.1 | B |
| Conducted radio frequency disturbance | IEC-60255-26:2023——6.2-6.5 | A |
| Fast transient bursts | IEC-60255-26:2023——6.2-6.5 | B |
| Slow damped oscillatory waves | IEC-60255-26:2023——6.2-6.4 | B |
| Surges | IEC-60255-26:2023——6.2-6.4 | B |
| Voltage dips and short interruptions test(AC or DC) | IEC-60255-26:2023——6.2 | A/C 1 |
| Magnetic field at power frequency | IEC-60255-26:2023——6.1 | B |