AM3SE Protection Relay

● A complete set of protection, related to the application ● 3 current input, 3 voltage input, 11DI, 5DO ● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V, DC48V, DC24V ● 1 RS485 serial communication, IEC60870-5-103 and Modbus-RTU ● 1 GPS for GPS timing ● More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records ● Powerful graphic programmable Logic

  • Fast And Safe Logistics
  • Sample Available

General

AM series microcomputer protection measurement and control device set protection, measurement, control in one, suitable for 35kV and below the voltage level of the user terminal substation (station), can achieve the protection and measurement and control of the user substation. Application fields cover power, water conservancy, transportation, petroleum, chemical, coal, metallurgy and other industries.

Front Panel

Technical Parameter

Power supplyRated inputAC/DC220V, or AC/DC110V, or DC48V, or DC24V
RangeRared Voltage × (1±20%)
Consumption≤10W (DC)
Rated VoltageRated inputAC 100V/100/V
Range1~120V
Accuracy±0.5%
Consumption≤0.5VA (single phase)
Rated CurrentRated inputAC 5A /1A
Range0.04In~15In
Accuracy±0.5%
Consumption≤0.5VA (single phase)
FrequenceRated frequency50Hz or 60Hz
Range45~55Hz or 60Hz
Accuracy±0.1Hz
DIRated VoltageAC/DC220V, or AC/DC110V, or DC48V, or DC24V
RangeRared Voltage × (1±20%)
Cconsumption≤1W (DC220V) (single channel)
DOMechanical life≥10000
Switching capacity≥1000W, L/R = 40ms
On currentcontinuous ≥5A, short time (200ms) ≥30A
Interrupting capacity≥30W, L/R = 40ms
EnvironmentTemperature-10℃~+55℃
Humidity5%~95% (No condensation and freeze inside)
Altitude≤4000m

Wiring

LCD Display

Installation Dimension

Typical Connection