ALP500 Low Voltage Protection and Control Relay

● Integrate leakage, overload and earth fault protection ● Comprehensive protection functions ● High accuracy energy metering ● Support Modbus-RTU、Modbus-TCP、Profibus-DP Communication ● 2nd~63rd harmonic measurement ● Wired Temperature measurement - PT100、PT1000、NTC; Wireless Temperature measurement - ATE100、ATE200、ATE400 ● Suitable for AC 690V and below low-voltage switchgear, distribution panels and feeder circuits.

  • Fast And Safe Logistics
  • Sample Available

General

Acrel ALP500 low-voltage protection measurement and control device (hereinafter referred to as low-voltage protection device) is suitable for low-voltage power distribution circuit with rated voltage to AC660V, integrating power monitoring, feeder protection, opening and closing control, communication networking, node temperature measurement, operation and maintenance management and other functions.

It has various protection functions such as inverse time overcurrent, three-stage overcurrent, overpower, zero sequence overcurrent, undervoltage, overvoltage, unbalance (voltage, current), neutral line overcurrent, and leakage current. Different communication modules can be selected to meet the needs of on-site communication.


The product adopts embedded installation and consists of a main body, a transformer and optional functional modules.

Function

1) Dynamically adjusts protection strategy based on cable heating characteristics to prevent overload burnout;

2) Zero-sequence/leakage current protection;

3) Accurately detects grounding faults to prevent electric shock and fire;

4) Temperature-linked protection;

5) Equipped with wired/wireless temperature measurement modules, it monitors busbar and node temperatures in real time, providing automatic over-temperature warnings;

6) Voltage/current imbalance protection;

7) Promptly detects three-phase imbalances to reduce equipment losses.

Additional Function

Additional FunctionsCode NameAdditional FunctionsCode Name
2-63rd harmonic voltage and currentHWaveform recordWR
Communication Module(Choose one)1*Profibus DPV0 CommunicationCPLeakage protectionL
2*Profibus DPV0 Communication2CPMetering moduleS
Ethernet Communication (Modbus-TCP protocol)MCE1*4-20mA Analog outputM1
4G4G2*4-20mA Analog outputM2
LoraLORASwitch moduleMD

Technical Parameter

Technical ParametersTechnical Indicators
Auxiliary PowerSupport AC 85-265V/DC 100-300V, Wide range power input
Rated VoltageAC 380V / 660V,50Hz / 60Hz
Rated Current1 (0.5A-6300A)XXX/1A Transformer with external CT
5 (0.5A-6300A)XXX/5A Transformer with external CT
25 (6A-25A)external current transformer
100 (25A-100A)
AccuracyProtectionAccuracy3-phase Current1.0 Class
3-phase Voltage0.5 Class
Power, Electrical Energy2.5 Class
MeasuringAccuracy3-phase Current、Voltage0.5 Class
Active Power, Electrical Energy0.5 Class
Reactive Power, Electrical Energy1.0 Class
Relay OutputContact CapacityStandard configuration 4 channelsResistive load、AC250V/10A
Optional 3 channels
Digital InputStandard configuration 4 channels passive dry junctionOptional active DC110V、DC220V、AC220V input
Optional10 channels passive dry junction
CommunicationStandard configuration2*MODBUS RTU Communication
Optional (Choose one)1*MODBUS-TCP
1*PROFIBUS-DPV0
2*PROFIBUS-DPV0
1*4G Communication
1*Lora Communication
Application EnvironmentWorking Temperature-10ºC~55ºC
Storage temperature-25ºC~70ºC
Relative humidity≤95%, No condensation, No corrosive gas
Altitude≤2000m
Pollution Level3 Class
Protection GradeMain Body IP54, Additional function modules IP20
Installation TypeIII Class

Dimension

Dimension of current transformer
Dimension of main body & additional functional module

Typical Connection