● Inverse-time Overcurrent & Earth-fault ● Three-stage Definite-time Overcurrent & Earth-fault ● Current Unbalance Protection ● Residual Current Monitoring

| Technical parameter | Qualification | ||
| Accessory power supply | Voltage range | AC/DC 85~265V | |
| Power dissipation | |||
| Import | Current specifications | ABCN (4-channel): 1A/5A | 10%Ie~1000%Ie ±2% |
| Residual currentspecification | 30mA-1000mA | ±2% | |
| Frequency | 45Hz-65Hz | ±0.2Hz | |
| Output | Output method | Dual-channel single-pole double-throw switch | |
| Output capacity | Resistive load; AC 250 V 5 A / DC 30 V 5 A | ||
| Installation andUsage Environment | Workplace Scenario | No direct exposure to rain or snow; no corrosive gases; no severe vibration | |
| Relative humidity | ≤95% RH, no condensation | ||
| Working temperature | -20℃~+70℃ | ||
| Storage temperature | -40℃~+70℃ | ||
| Height | ≤2000m | ||
| Way to install | Embedded installation: 88×88 (mm) | ||
| Levels of protection | Panel: IP54; Terminals: IP20 | ||
| Security classification | EMC | Level III | |
| Function | Standard configuration | Optional | |
| Measurement Function | Three-phase alternating current | √ | |
| Neutral conductor current | √ | ||
| Residual current | √ | ||
| Defencive function | Inverse-time overcurrent protection | √ | |
| Inverse Time Grounding | √ | ||
| Three-stage time-delayedovercurrent protection | √ | ||
| Three-stage time-delayedground fault protection | √ | ||
| Current imbalance | √ | ||
| Leakage current | √ | ||
| Communication Function | Modbus-RTU | √ | |
| Digital output function | 2 Single-pole double-throw switch | √ | |
| Record Function | 20 Single fault record | √ | |
| 20 Event Record | √ | ||
| Display Function | Liquid-crystal display | √ | |
| Setpoint Setting Function | Operation Panel Modification | √ | |
| Communication Amendment | √ | ||